Rogue7: Rogue Engineering-Station Attacks on S7 Simatic PLCs

The Siemens industrial control systems architecture consists of Simatic S7 PLCs which communicate with a TIA engineering station and SCADA HMI on one side, and control industrial systems on the other side. The newer versions of the architecture are claimed to be secure against sophisticated attackers, since they use advanced cryptographic primitives and protocols. In this paper we show that even the latest versions of the devices and protocols are still vulnerable.

After reverse-engineering the cryptographic protocol, we are able to create a rogue engineering station which can masquerade as the TIA to the PLC and inject any messages favourable to the attacker. As a first example we extend attacks that can remotely start or stop the PLC to the latest S7-1500 PLCs. Our main attack can download control logic of the attacker's choice to a remote PLC. Our strongest attack can separately modify the running code and the source code, which are both downloaded to the PLC. This allows us to modify the control logic of the PLC while retaining the source code the PLC presents to the engineering station. Thus, we can create a situation where the PLC's functionality is different from the control logic visible to the engineer.

Presented by